Miniature Amplified Low Pressure Sensors
Download datasheet (PDF)
Download dimensional drawing (PDF)
Features
- 0 to 1" H2O to 0 to 30" H2O Pressure Ranges
- Matched pressure port volumes
- Temperature Compensated
- Calibrated Zero and Span
Applications
- Medical Instrumentation
- Environmental Controls
- HVAC
General Description
The Miniature Amplified Output pressure sensors is based upon a proprietary technology to reduce all output offset or common mode errors. This model provides a calibrated amplified output with superior output offset characteristics. Output offset errors due to change in temperature, stability to warm-up, stability to long time period, and position sensitivity are all significantly reduced when compared to
conventional compensation methods. In addition the sensor utilizes a silicon, micromachined, stress concentration enhanced structure to provide a very linear output to measured pressure.
These calibrated and temperature compensated sensors give an accurate and stable output over a wide temperature range. This series is intended for use with non-corrosive, non-ionic working fluids such as air, dry gases and the like.
The output of the device is ratiometric to the supply voltage and operation from any D.C. supply voltage between 4.5 and 5.5 volts.
Pressure Sensor Characteristics Maximum Ratings
- Supply Voltage Vs: +4.5 to +5.5 Vdc
- Common-mode pressure: 10 psig
- Lead Temperature (soldering 2-4 sec.): 250°C
Environmental Specifications
Temperature Ranges
- Compensated: 5 to 50°C
- Operating: -25 to 85°C
- Storage: -40 to 125°C
- Humidity Limits: 0 to 95% RH (non-condensing)
Standard Pressure Ranges
| Part Number |
Operating Pressure |
Nominal Span |
Proof Pressure |
Burst Pressure |
1 INCH-Dx-4V-MINI
|
± 1 In H2O
|
4V |
100 In H20 |
200 In H20 |
| 1 INCH-G-4V-MINI |
0 - 1 In H2O |
4V |
100 In H20 |
200 In H20 |
| 5 INCH-Dx-4V-MINI |
± 5 In H2O |
4V |
200 In H20 |
300 In H20 |
| 5 INCH-G-4V-MINI |
0 - 5 In H2O |
4V |
200 In H20 |
300 In H20 |
| 10 INCH-Dx-4V-MINI |
± 10 In H2O |
4V |
200 In H20 |
300 In H20 |
| 10 INCH-G-4V-MINI |
0-10 In H2O |
4V |
200 In H20 |
300 In H20 |
| 20 INCH-Dx-4V-MINI |
± 20 In H2O |
4V |
300 In H20 |
500 In H20 |
| 20 INCH-G-4V-MINI |
0-20 In H2O |
4V |
300 In H20 |
500 In H20 |
| 30 INCH-Dx-4V-MINI |
± 30 In H2O |
4V |
500 In H20 |
800 In H20 |
| 30 INCH-G-4V-MINI |
0-30 In H2O |
4V |
500 In H20 |
800 In H20 |
Performance Characteristics for 1 INCH-Dx-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, differential pressure |
-- |
± 1.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
± 1.9 |
± 2.0 |
± 2.10 |
V |
| Offset Voltage @ zero differential pressure |
2.15 |
2.25 |
2.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 60 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 10 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 5 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 10 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 2 |
%span |
Performance Characteristics for 1 INCH-G-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, gage pressure |
-- |
± 1.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
3.90 |
± 4.0 |
± 4.10 |
V |
| Offset Voltage @ zero pressure |
0.15 |
0.25 |
0.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 60 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 10 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 15 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 10 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 2 |
%span |
Performance Characteristics for 5 INCH-Dx-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, differential pressure |
-- |
± 5.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
± 1.9 |
± 2.0 |
± 2.10 |
V |
| Offset Voltage @ zero differential pressure |
2.15 |
2.25 |
2.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 40 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 5 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 5 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 5 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 1 |
%span |
Performance Characteristics for 5 INCH-G-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, gage pressure |
-- |
5.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
3.90 |
4.0 |
4.10 |
V |
| Offset Voltage @ zero pressure |
0.15 |
0.25 |
0.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 40 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 5 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 5 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 5 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 1 |
%span |
Performance Characteristics for 10 INCH-Dx-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, differential pressure |
-- |
± 10.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
± 1.9 |
± 2.0 |
± 2.10 |
V |
| Offset Voltage @ zero differential pressure |
2.15 |
2.25 |
2.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 20 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 5 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 5 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 5 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 1 |
%span |
Performance Characteristics for 10INCH-G-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, gage pressure |
-- |
10.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
3.90 |
4.0 |
4.10 |
V |
| Offset Voltage @ zero pressure |
0.15 |
0.25 |
0.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 20 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 5 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 5 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 5 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 1 |
%span |
Performance Characteristics for 20 INCH-Dx-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, differential pressure |
-- |
± 20.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
± 1.9 |
± 2.0 |
± 2.10 |
V |
| Offset Voltage @ zero differential pressure |
2.15 |
2.25 |
2.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 20 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 5 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 5 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 5 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 1 |
%span |
Performance Characteristics for 20INCH-G-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, gage pressure |
-- |
20.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
3.90 |
4.0 |
4.10 |
V |
| Offset Voltage @ zero pressure |
0.15 |
0.25 |
0.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 20 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 5 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 5 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 5 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 1 |
%span |
Performance Characteristics for 30 INCH-Dx-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, differential pressure |
-- |
± 30.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
± 1.9 |
± 2.0 |
± 2.10 |
V |
| Offset Voltage @ zero differential pressure |
2.15 |
2.25 |
2.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 20 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 5 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 5 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 5 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 1 |
%span |
Performance Characteristics for 30INCH-G-4V-MINI
| Parameter, note 1 |
Minimum |
Nominal |
Maximum |
Units |
| Operating Range, gage pressure |
-- |
30.0 |
-- |
" H2O |
| Output Span, @ 1" H2O, note 5 |
3.90 |
4.0 |
4.10 |
V |
| Offset Voltage @ zero pressure |
0.15 |
0.25 |
0.35 |
V |
| Offset Temperature Shift (0°C-50°C), note 2 |
-- |
-- |
± 20 |
mV |
| Offset Warm-up Shift, note 3 |
-- |
± 5 |
-- |
mV |
| Offset Position Sensitivity (±1g) |
-- |
± 5 |
-- |
mV |
| Offset Long Term Drift (one year) |
-- |
± 5 |
-- |
mV |
| Linearity, hysteresis error, note 4 |
-- |
0.05 |
0.25 |
%fs |
| Span Shift (5°C-50°C), note 2 |
-- |
-- |
± 1 |
%span |
Specification Notes
(1): All parameters are measured at 5.0 volt excitiation, for the nominal full scale pressure and room temperature unless otherwise specified. Pressure measurements are with positive pressure applied to port B.
(2): Shift is relative to 25°C.
(3): Shift is within the first hour of excitation applied to the device.
(4) Measured at one-half full scale rated pressure using best straight line curve fit.
(5): The voltage added to the offset voltage at full scale pressure. Nominally the output voltage range is 0.25 to 4.25 volts for minus to plus full scale pressure.
Pressure Response: for any pressure applied the response time to get to 90% of pressure applied is typically less than 500 useconds.
All Sensors reserves the right to make changes to any products herein. All Sensors does not assume any liability arising out of the application or use of any product or circuit described herein, neither does it convey any license under its patent rights nor the rights of others.